Description
The JDZX10-10 Voltage Transformer is a single-phase, epoxy-cast transformer equipped with a residual voltage winding. It is ideal for 10kV power systems operating at 50Hz or 60Hz and is widely used for voltage measurement, energy metering, and relay protection applications.
Model Meaning
-
J – Voltage Transformer
-
D – Single-phase
-
Z – Epoxy-cast insulation
-
X – With residual voltage winding
-
10 – Design number
-
10 – Rated voltage (10kV)
Technical Specifications
-
Primary Voltage: 10kV
-
Secondary Voltage: 100V (standard)
-
Residual Voltage Winding: 100/3V
-
Frequency: 50Hz or 60Hz
-
Accuracy Classes & Rated Capacity:
-
0.2 – 50–100VA (high-precision metering)
-
0.5 – 100–200VA (general measurement)
-
3 – 200–400VA (relay protection)
-
-
Insulation Levels:
-
Primary-to-ground: 12/42/75kV (rated voltage / short-time withstand / lightning impulse)
-
Secondary-to-ground: 3kV, 1 min
-
Structural Features
-
Compact & Durable: Single-phase, epoxy-cast structure offers moisture, dust, and corrosion resistance.
-
Winding Design: High-strength insulated primary winding; secondary and residual windings are fully isolated for accuracy and reliability.
-
Housing: Smooth, weather-resistant epoxy resin shell for long-term durability.
Installation & Usage
-
Inspect for physical damage and verify nameplate parameters.
-
Measure insulation resistance: primary ≥ 1000MΩ, secondary ≥ 10MΩ.
-
Can be installed inside switchgear or on a dedicated mounting bracket.
-
Ensure secure mounting with correct alignment; connect high-voltage and secondary circuits properly.
-
Do not short-circuit secondary winding; residual voltage winding must be grounded during normal operation.
-
Perform regular operational checks and preventive tests (insulation resistance, dielectric loss, voltage withstand).
Maintenance & Inspection
-
Daily: Clean surface, tighten terminals, check secondary circuit fuses.
-
Routine Inspection: Every 3–5 years for full maintenance including visual inspection and electrical testing.
-
Replace damaged components and verify performance.
Transportation & Storage
-
Avoid severe vibration, collision, and inversion during transport; use proper packaging.
-
Store indoors in a dry, ventilated area at -25°C to +40°C with humidity below 85%.
-
Periodically inspect appearance and insulation condition during storage.