Ceritified

CE、TUV、CB、RoHS

Service

ODM & OEM

Ceritified

ISO 9001:2008

IEC and IEEE/ANSI describe the same medium-voltage switchgear with two different rating systems, and the differences are not cosmetic. A 13.8 kV system in the United States uses 15 kV class equipment with a 95 kV basic impulse level; the IEC equivalent for a 13.8 kV system is a 17.5 kV rated assembly with 95 kV lightning impulse and a 38 kV power-frequency withstand. Same job, different numbers, different drawings, different type test reports.

This article compares the two frameworks as they apply to metal-enclosed medium-voltage switchgear: which standard covers what, how the voltage and insulation ratings map to each other, where fault ratings diverge, and what to write in a specification so the equipment you receive can be reviewed against the standard you must follow.

The Short Answer

IEC 62271-200 governs metal-enclosed switchgear from above 1 kV to 52 kV, with circuit breakers covered by IEC 62271-100 and common requirements in IEC 62271-1. In North America, IEEE C37.20.2 covers metal-clad switchgear, C37.20.3 covers metal-enclosed interrupter switchgear, and the breaker itself is rated under IEEE C37.04 and C37.06 and tested under C37.09.

Both systems produce safe, well-tested equipment. The practical problem is that a design compliant with one is not automatically compliant with the other, and the gap shows up in insulation levels, fault duration, and the acceptance tests a reviewer will ask to see.

Comparing the Core Documents

SubjectIEC frameworkIEEE / ANSI framework
Common requirementsIEC 62271-1IEEE C37.04 (rating structure)
Circuit breakers above 1 kVIEC 62271-100IEEE C37.04, C37.06, C37.09
Metal-clad switchgearIEC 62271-200IEEE C37.20.2
Metal-enclosed interrupter switchgearIEC 62271-103, 62271-200IEEE C37.20.3
Switches and earthing switchesIEC 62271-102, 62271-103IEEE C37.20.4
Instrument transformersIEC 61869-2 and 61869-3IEEE C57.13
Arc-resistant designIEC 62271-200 internal arc classIEEE C37.20.7
Application guideIEC 62271-1 annexes, IEC 60909IEEE C37.010
Comparison chart mapping IEC rated voltages of 7.2, 12, 17.5, 24, 36 and 40.5 kV against ANSI equipment classes of 5, 15 and 38 kV, showing where the two insulation level tables overlap and diverge.

Voltage Ratings: Where the Difference Bites

IEC rates equipment by its maximum voltage for equipment (Um), and the preferred values are 3.6, 7.2, 12, 17.5, 24, 36 and 40.5 kV. ANSI rates equipment by a class that sits one step above the nominal system voltage: a 13.8 kV system uses 15 kV class switchgear, a 4.16 kV system uses 5 kV class, and a 34.5 kV system uses 38 kV class.

Nominal system voltageIEC rated voltage (Um)ANSI equipment classInsulation level, IECInsulation level, ANSI
4.16 kV7.2 kV5 kV60 kV LI / 20 kV PF60 kV BIL / 19 kV PF
6.6 / 11 kV12 kV15 kV75 kV LI / 28 kV PF95 kV BIL / 36 kV PF
13.8 kV17.5 kV15 kV95 kV LI / 38 kV PF95 kV BIL / 36 kV PF
22 kV24 kV—125 kV LI / 50 kV PFNo class
33 / 34.5 kV36 kV38 kV170 kV LI / 70 kV PF150 kV BIL / 80 kV PF

Two consequences follow. First, an IEC 12 kV panel is not interchangeable with a 15 kV class ANSI panel — the ANSI unit has a higher insulation level for the same nominal duty, which is why it costs more. Second, a 13.8 kV project specified in IEC terms will use 17.5 kV equipment, one full class above the ANSI equivalent. Buyers who compare a Chinese 12 kV quotation against a US 15 kV quotation are not comparing like with like.

Insulation Levels and Why They Differ

ANSI historically set insulation levels higher relative to system voltage than IEC did, reflecting lightning exposure on overhead North American distribution and a conservative safety margin. IEC insulation levels were revised over decades to align with statistical overvoltage studies across 50 Hz networks, and are generally lower for the same nominal voltage.

The practical effect is on clearance and creepage. A 15 kV class ANSI panel has larger phase-to-phase and phase-to-earth clearances than an IEC 12 kV panel, and its bushings, current transformers and cable terminators are dimensioned accordingly. That is also why US-pattern equipment looks physically larger for the same current rating — it is not overbuilt, it is built to a different insulation table.

Fault Ratings and Duty Cycles

Both systems rate breakers by rated short-circuit breaking current, but the surrounding data differs. IEC specifies rated short-time withstand current with a duration of 1, 3 or 4 seconds (3 s and 4 s dominate in practice) and a rated peak withstand current of 2.5 times the symmetrical value for 50 Hz systems, 2.6 for 60 Hz. IEEE C37.06 lists preferred momentary and short-time ratings, with the short-time rating historically based on a 2-second duration.

Duty cycles also differ in emphasis. IEC 62271-100 defines rated sequences such as O-0.3 s-CO-180 s-CO and states the auto-reclosing requirement explicitly. IEEE C37.06 lists preferred ratings with a related required capability that includes reclosing, but presents the sequence and the number of operations differently. When a factory quotes “20 kA for 3 s” against an IEEE specification that says “20 kA momentary, 2 s”, the equipment may well be acceptable — but somebody has to write down why, in the review comments.

Instrument Transformers and Protection

Current and voltage transformers sit inside the switchgear and carry their own standards. IEC uses IEC 61869-2 for current transformers and IEC 61869-3 for voltage transformers, with accuracy classes such as 0.2, 0.5, 5P and 10P and a rated burden expressed in VA. North America uses IEEE C57.13, with accuracy classes such as 0.3, 0.6, 1.2 and relaying classes C100, C200, C400, C800 expressed as a secondary terminal voltage.

These are not convertible by formula. A 5P20 CT and a C400 relaying CT may both suit the same feeder, but the burden calculation, the saturation behaviour and the way the relay setting is documented all differ. Our explanation of current versus voltage transformers covers the fundamentals, and the instrument transformer range shows the classes available.

Internal Arc and Personnel Safety

IEC 62271-200 requires internal arc testing to be declared as a classification, with an accessibility type (A for installation-restricted areas, B for walk-in areas, C for outdoor) and a defined arc current and duration, typically 1 second. Arc-resistant designs are tested with indicators placed around the enclosure, and the result is expressed as IAC class A FLR or B FLR, where F, L and R denote front, lateral and rear accessibility.

IEEE addresses the same risk through C37.20.7, which defines accessibility types 1, 2, 2B, 2C and 3 and requires the design to be tested with the designated sides accessible. The philosophy is similar, the labelling is not. A specification that simply says “arc resistant” without naming the standard, the current, the duration and the accessibility type is a specification that cannot be verified.

Can One Design Satisfy Both?

Sometimes. A manufacturer can build a panel that meets IEC 62271-200 and additionally satisfies the IEEE insulation and rating tables, but this is a deliberate engineering exercise with separate type tests, not a documentation swap. Ratings that are easy to align are the electrical ones — 630 A and 20 kA mean the same thing in both systems. The hard parts are insulation levels, fault duration, arc classification and the instrument transformer classes.

If your project spans both worlds — a Chinese-built substation reviewed by a US-based engineer, for example — the cleanest approach is to nominate the governing framework in the specification, then list the specific clauses of the other framework that must also be demonstrated. Expect the supplier to price the additional type testing.

What to Write in the Specification

  • Name the governing standard family and edition for the assembly and for the breaker.
  • State rated voltage in the terms of that standard: Um in kV, or equipment class in kV.
  • Give insulation levels explicitly: lightning impulse and power-frequency withstand, phase-to-phase, phase-to-earth and across the open gap.
  • State short-circuit breaking current, short-time withstand current and the duration in seconds.
  • State the internal arc classification, current, duration and accessibility type.
  • Specify the CT and VT standard, accuracy class and burden, including the relaying class.
  • List the type test reports required, by test name, not by report number.
  • State ambient temperature, altitude and seismic requirement, since both frameworks derate from standard conditions.

For breaker technology selection inside that framework, our comparison of vacuum and SF₆ circuit breakers covers where each is normally applied, and the vacuum circuit breaker range shows the ratings that are commonly available off catalogue.

Conclusion

IEC and IEEE describe equivalent equipment with different rating bases, different insulation tables and different test reporting. The voltages that look familiar are the ones that catch people out: 13.8 kV maps to 17.5 kV under IEC and 15 kV class under ANSI, and those are not the same panel. Write the governing standard into the specification, state the insulation and arc ratings numerically, and require the type test reports by test name. If you need a design reviewed against both frameworks, send the ratings table and we will mark up where the two diverge.

FAQ

Is IEC 62271 the same as IEEE C37?

No. They cover the same equipment families but use different rating structures, insulation tables and test procedures. IEC 62271-200 is the assembly standard for metal-enclosed switchgear up to 52 kV; IEEE C37.20.2 covers metal-clad switchgear in North America.

Can IEC switchgear be installed in the United States?

Technically it can be installed, but acceptance depends on the authority having jurisdiction and on the project specification, which usually references UL and IEEE requirements. Equipment must be evaluated against those requirements, not assumed compliant.

Why is ANSI insulation higher than IEC for the same voltage?

ANSI insulation levels were historically set with a larger margin above nominal system voltage, partly reflecting lightning exposure on overhead distribution. IEC levels were revised against statistical overvoltage studies and are generally lower for the same nominal voltage.

What is the IEC equivalent of 15 kV switchgear?

There is no exact equivalent. A 15 kV class ANSI panel has a 95 kV BIL, which matches IEC 17.5 kV equipment on lightning impulse, but the power-frequency withstand and the clearance requirements differ.

Previous Post

11kV Switchgear, 22kV and 33kV: VCB Selection Guide

Next Post

Type Test vs Routine Test for Switchgear: What's the Difference

Related Posts

Get A Free Quote
Get more information about our products
+86-15988773632 Phone sales01@cnsovio.com E-mail